|
Legacy Part No. |  | W389DZCX-2
|  | Nominal Input Voltage |  | 12 VDC
|  | Coil Resistance |  | 100 Ohm
|  | Cover Style |  | Flange Cover
|  | Options |  | Flag Indicator
|  | Weight |  | 88 G
|  |
| |
|
Contact Rating |  | 30 A
|  | Contact Configuration |  | SPDT-DM-DB
|  | Contact Materials |  | Silver Alloy
|  | Maximum Switching Voltage |  | 600 V
|  | Switching Current at Voltage (AC, Resistive) |  | 30 A at 300 V 50 / 60 Hz
|  | Switching Current at Voltage (DC, Resistive) |  | 30 A at 28 VDC
|  | Switching Current at Voltage (Pilot Duty) |  | A600
|  | Minimum Switching Requirement |  | 100 mA at 5 VDC or 0.5 W
|  |
| |
|
Operating Range - % of Nominal (AC) |  | 85 to 110 %
|  | Operating Range - % of Nominal (DC) |  | 80 to 110 %
|  | Average Consumption (AC) |  | 3.5 VA
|  | Average Consumption (DC) |  | 1.44 W
|  | Drop-out Voltage Threshold (DC) |  | 10 %
|  | Drop-out Voltage Threshold (AC) |  | 10 %
|  |
| |
|
Electrical Life (UL508), Operations at Rated Current (Resistive) |  | 100000
|  | Mechanical Life, Unpowered |  | 5000000
|  | Operating Time (Response Time) |  | 20 ms
|  |
| |
|
Ambient Air Temperature around the Device - Storage |  | -40 to +85 °C
|  | Ambient Air Temperature around the Device - Operation |  | -40 to +55 °C
|  |
| |
|
Agency Approvals |  | UL CE CSA
|  |
| |